HOTLINE
RM Series Rack-Mounted Modular Online UPS 25-200kVA of INVT brand is a scalable, hot-swappable, double -conversion Online UPS. With DSP (Digital Signal Processing) and advanced 3 level IGBT technology, RM Series Rack-Mounted Modular 25-200kVA has great flexibility and reliability, making it the ideal choice for today’s data centers.
For fastest support.
Please call 1800 6567 (Free of charge)
RM Series Rack-Mounted Modular with capacity 25 – 200kVA is an Online UPS line that integrates INVT’s double conversion technology, expandable, hot maintenance. With advanced DSP (Digital Signal Processing) and IGBT control technology, the RM Series Rack-Mounted Modular with a capacity of 25-200kVA has great flexibility and reliability, making it the ideal choice for today’s data centers great.
| MODEL | RM150/25C | RM200/25C | |||
| System Capacity | 150kVA | 200kVA | |||
| Power Module Capacity | 25kVA/25kW | ||||
| Input | Dual Input | Optional | Standard | ||
| Phase | 3 Phase + Neutral + Ground, 380V/400V/415V (line-line) | ||||
| Input Voltage Range | 304~478Vac (line-line), full load;
228V~304Vac (line-line), load decreases linearly according to the min phase voltage |
||||
| Rate Frequency | 50/60Hz | ||||
| Input Frequency Range | 40Hz~70Hz | ||||
| Input PF | >0.99 | ||||
| Input THDi | <3% (100% Linear load) | ||||
| Bypass | Rate Voltage | 380/400/415Vac (line-line) | |||
| Rate Frequency | 50/60Hz | ||||
| Input Voltage Range | Settable, -40%~+25% | ||||
| Bypass Frequency Range | Settable, ±1Hz, ±3Hz, ±5Hz | ||||
| Bypass Overload | 110% long term operation; 125% for 5 mins; 150% for 1 min; >150% for 1s | ||||
| Output | Rate Voltage | 380/400/415Vac (line-line) | |||
| Voltage Regulation | ±1 (0~100% linear load) | ||||
| Rate Frequency | 50/60Hz | ||||
| Frequency Precision | 0.1% | ||||
| Output PF | 1 | ||||
| Output THDu | <1%, Linear load; <6%, Non-linear load | ||||
| Crest Factor | 3:1 | ||||
| Inverter Overload | 110% for 1 hour; 125% for 10 mins; 150% for 1 min; >150% for 200ms | ||||
| Battery | Voltage | ±240Vdc | |||
| Battery Number | 40pcs (Settable: even number from 32 to 44) | ||||
| Voltage Precision | ±1% | ||||
| Charge Power | up to 20% * Output active power | ||||
| Battery Cold Start | Standard | ||||
| System | Efficiency | AC Mode | 96.0% | ||
| ECO Mode | 98.0% | ||||
| Battery Mode | 95.5% | ||||
| Display | 7.0″ color touch screen LCD + LED + keyboard | ||||
| IP Class | IP 20 | ||||
| Interface | RS232, RS485, Programmable Dry Contact | ||||
| Option | PDU for RM150/25C, SNMP Card, Parallel kit, SPD, LBS | ||||
| Temperature | Operation: 0~40 ℃ Storge: -40~70 ℃ | ||||
| Relative Humidity | 0~95% Non-condensing | ||||
| Altitude | <1000m. Within 1000m to 2000m, 1% power derating for every 100m rise. | ||||
| Noise (1 meter) | 65dB @ 100% load, 62dB @ 45% load | ||||
| Applicable Standards | Safety: IEC/EN 62040-1 EMC: IEC/EN 62040-2 Performance: IEC/EN 62040-3 | ||||
| Physical | Weight (kg) | Cabinet | 140 | 160 | |
| Power module | 18 | ||||
| Dimension W*D*H (mm) | Cabinet | 482*916*931 | 482*916*1550 | ||
| Power module | 436*677*85 | ||||