HOTLINE
RM Series modular UPS, 20 – 200kVA of INVT brand is an Online UPS for sensitive electronic equipment. With DSP (Digital Signal Processing) and advanced 3 level IGBT technology, RM Series Modular 20-200kVA delivers the best of combination of reliability, hot-swappable and flexibility.
For fastest support.
Please call 1800 6567 (Free of charge)
The RM Series modular UPS with a capacity of 20 – 200kVA of INVT brand is an Online UPS line for sensitive electronic equipment. With advanced DSP (Digital Signal Processing) and IGBT control technology, the RM Series Modular with a capacity of 20-200kVA is the perfect combination of reliability, hot maintenance and flexibility.
MODEL | RM200/20 | RM120/20 | RM060/20 | ||||
System Capacity | 200kVA | 120kVA | 60kVA | ||||
Power Module Capacity | 20kVA/18kW | ||||||
Input | Dual Input | Optional | |||||
Phase | 3 Phase + Neutral + Ground, 380V/400V/415V (line-line) | ||||||
Input Voltage Range | 304~478Vac (line-line), full load;
228V~304Vac (line-line), load decreases linearly according to the min phase voltage |
||||||
Rate Frequency | 50/60Hz | ||||||
Input Frequency Range | 40Hz~70Hz | ||||||
Input PF | >0.99 | ||||||
Input THDi | <3% (100% Linear load) | ||||||
Bypass | Rate Voltage | 380/400/415Vac (line-line) | |||||
Rate Frequency | 50/60Hz | ||||||
Input Voltage Range | Settable, -40%~+25% | ||||||
Bypass Frequency Range | Settable, ±1Hz, ±3Hz, ±5Hz | ||||||
Bypass Overload | 125% long term operation; 130% for 1 hour ;150% for 6 mins; 1000% for 100ms | ||||||
Output | Rate Voltage | 380/400/415Vac (line-line) | |||||
Voltage Regulation | 1% for balance load; 1.5% for unbalance load | ||||||
Rate Frequency | 50/60Hz | ||||||
Frequency Precision | 0.1% | ||||||
Output PF | 0.9 | ||||||
Output THDu | <1%, Linear load; <5.5%, Non-linear load | ||||||
Crest Factor | 3:1 | ||||||
Inverter Overload | 110% for 1 hour; 125% for 10 mins ;150% for 1 min; >150% for 200 ms | ||||||
Battery | Voltage | ±240Vdc | |||||
Battery Number | 40pcs (Settable: even number from 32 to 44) | ||||||
Voltage Precision | ±1% | ||||||
Charge Power | up to 20% * Output active power | ||||||
Battery Cold Start | Standard | ||||||
System | Efficiency | AC Mode | 95.0% | ||||
ECO Mode | 99.0% | ||||||
Battery Mode | 95.0% | ||||||
Display | 5.7″ touch screen LCD + LED + keyboard | ||||||
IP Class | IP 20 | ||||||
Interface | RS232, RS485, Programmable Dry Contact | ||||||
Option | SNMP Card, Parallel kit, SPD, LBS, Dust filter | ||||||
Temperature | Operation: 0~40 ℃ Storge: -40~70 ℃ | ||||||
Relative Humidity | 0~95% Non-condensing | ||||||
Altitude | <1000m. Within 1000m to 2000m, 1% power derating for every 100m rise. | ||||||
Noise (1 meter) | 55dB @ 50% load | ||||||
Applicable Standards | Safety: IEC/EN 62040-1 EMC: IEC/EN 62040-2 Performance: IEC/EN 62040-3 | ||||||
Physical | Weight (kg) | Cabinet | 180 | 150 | 105 | ||
Power module | 22 | ||||||
Dimension W*D*H (mm) | Cabinet | 600*900*2000 | 600*900*1600 | 600*900*1100 | |||
Power module | 440*590*134 |