HT11 Series Tower Online UPS 1-3kVA (220V/230V/240V) with in-built battery

HT11 Series Tower Online UPS 1-3kVA (220V/230V/240V) with in-built battery

HT11..S UPS (with in-built battery) 1 – 3kVA of INVT brand is a double-conversion online UPS with full DSP (Digital Signal Processing) control technology. With high input and output power factor, self-adjusting output frequency and network management, HT11..S 1 – 3kVA is a perfect choice for computers, telecommunication equipment and other sensitive devices.

Request a quote

For fastest support.

Please call 1800 6567 (Free of charge)

The HT11..S UPS (with built-in battery) with a capacity of 1 – 3kVA of the INVT brand is a dual-conversion Online UPS line that integrates DSP (Digital Signal Processing) control technology. With high input and output power factor, self-regulating output frequency and network management, the HT11..S capacity 1 – 3kVA is the perfect choice for computers, telecommunications equipment and other devices. sensitive electronics.

00 +

YEARS OF EXPERIENCE

00 +

TALENTS

00 +

CUSTOMER

Detailed Product Description

Application

IDC (Internet Dater Center), network, servers and workstations, control system, communication system, office, PC etc

Features

  • Wide range of input voltage while input PF > 97%
  • Output power factor of 0.9, more powerful load capability
  • Full Protection of over-voltage, circuit short and over temperature
  • LCD/LED display, monitoring all the operation status
  • Auto fan speed adjustment.
  • In-built output transformer for TX branch.

Request a quote

    MODEL HT1101S HT1102S HT1103S
    Capacity 1kVA 2kVA 3kVA
    Phase Single Phase in, Single Phase out
    Input Voltage 110Vac-288Vac
    100% load@>176Vac; 80% load@>154Vac;

    70% load@>132Vac; 50% load@>110Vac

    Input PF >0.97
    Input Frequency 40Hz~70Hz
    Output PF 0.9 (0.8 for TX branch)
    Output Voltage 220V/230V/240V
    Voltage Regulation ± 1 % (±5% for TX branch)
    THDu ≤2% (linear)
    ≤5.5% (non-linear) ≤5.0% (non-linear) ≤5.0% (non-linear)
    Crest Factor 3:1
    Efficiency 87.0% (80% for TX branch) 91.0% (81% for TX branch) 90.0% (81% for TX branch)
    Noise <43dB@<70%Load,

    <47dB@>70%Load

    <45dB@<70%Load,

    <50dB@>70%Load

    <45dB@<70%Load,

    <50dB@>70%Load

    Overload Capability Inverter 105%~130%: to bypass after 1 min;

    150%: to bypass after 30 sec

    Battery 105%~130%: shut down after 10 sec;

    150%: shut down after 5 sec

    Battery Voltage 36Vdc 72Vdc 96Vdc
    Battery Type/Number 12V, 7Ah*3 12V, 7Ah*6 12V, 7Ah*8
    Max Charging Current 1A
    Interface RS232, EPO
    Optional USB (B Type), SNMP, Dry contact
    W*D*H (mm) 144*353*222 190*374*336 190*374*336
    Weight (kg) 10.5 21 24.5