HOTLINE
HR33 UPS is double conversion online UPS with fully DSP (Digital Signal Processing) controlled technology. With its flexible configuration of 3/3 and 3/1 compact design, it’s the ideal choice for modern data center.
For fastest support.
Please call 1800 6567 (Free of charge)
The dual-conversion UPS HR33 series is fully integrated with DSP (Digital Signal Processing) control technology. With flexible configurations of 3 phase in 3 phase out and 3 phase in 1 phase out, compact design, this product line is well suited for modern data centers.
| MODEL | HR33010CL | HR33015CL | HR33020CL | HR33025CL | ||
| System Capacity | 10kVA | 10kVA | 20kVA | 25kVA | ||
| Input | Dual Input | Standard | ||||
| Phase | 3 Phase+Neutral+Ground, 380V/400V/415V(line-line) | |||||
| Input Voltage Range | 304~478Vac (line-line),full load;
228V~304Vac (line-line),load decreases linearly according to the min phase voltage |
|||||
| Rate Frequency | 50/60Hz | |||||
| Input Frequency Range | 40Hz~70Hz | |||||
| Input PF | >0.99 | |||||
| Input THDi | <4% (100% Linear load) | <3% (100% Linear load) | ||||
| Bypass | Rate Voltage | 380/400/415Vac (line-line) | ||||
| Rate Frequency | 50/60Hz | |||||
| Input Voltage Range | Settable, -40%~+25% | |||||
| Bypass Frequency Range | Settable, ±1Hz, ±3Hz, ±5Hz | |||||
| Bypass Overload | 125% long term operation; 130% for 10 mins; 150% for 1 min, 400% for 1s | |||||
| Output | Rate Voltage | 380/400/415Vac (line-line) | ||||
| Voltage Regulation | 1% for balance load; 1.5% for unbalance load | |||||
| Rate Frequency | 50/60Hz | |||||
| Frequency Precision | 0.1% | |||||
| Output PF | 1 | |||||
| Output THDu | <1% , Linear load; <5.5%, Non-linear load | <1.5% , Linear load; <6%, Non-linear load | ||||
| Crest Factor | 3:1 | |||||
| Inverter Overload | 110% for 1 hour; 125% for 10 mins ;150% for 1 min; >150% for 200 ms | |||||
| Battery | Voltage | ±240Vdc | ||||
| Battery Number | 40pcs (Settable: even number from 32 to 44) | |||||
| Voltage Precision | ±1% | |||||
| Charge Power | up to 20% * Output active power | |||||
| Battery Cold Start | Standard | |||||
| System | Efficiency | AC Mode | 95% | 95.5% | ||
| ECO Mode | 98% | |||||
| Battery Mode | 94.5% | 95% | ||||
| Display | LCD + LED + keyboard | |||||
| IP Class | IP 20 | |||||
| Interface | RS232, RS485, Programmable Dry Contact | |||||
| Option | LBS for HR33020CL and HR33025CL, SNMP Card, Parallel kit, USB | |||||
| Temperature | Operation: 0~40 ℃ Storge: -40~70 ℃ | |||||
| Relative Humidity | 0~95% Non-condensing | |||||
| Altitude | <1000m. Within 1000m to 2000m, 1% power derating for every 100m rise | |||||
| Noise (1 meter) | 65dB @ 100% load, 62dB @ 45% load | |||||
| Applicable Standards | Safety: IEC/EN 62040-1 EMC: IEC/EN 62040-2 Performance: IEC/EN 62040-3 | |||||
| Physical | Weight (kg) | 25 | 30 | |||
| Dimension W*D*H (mm) | 485*750*130 | |||||