HOTLINE
RM Series Rack-Mounted Modular Online UPS 10-90kVA of INVT brand is a scalable, hot-swappable, double -conversion Online UPS. With its flexible configuration of 3/3, 3/1 and 1/1, compact structure, this RM series is the ideal choice for small and medium data center.
For fastest support.
Please call 1800 6567 (Free of charge)
RM Series Rack-Mounted Modular with capacity of 10 – 90kVA is an Online UPS line that integrates INVT’s double conversion technology, expandable, hot maintenance. With a flexible configuration of 3 phase in 3 phase out, 3 phase in 1 phase out and 1 phase in 1 phase out, compact design, this RM series is the ideal choice for small and medium data centers.
MODEL | RM060/10X | RM040/10X | RM020/10X | RM090/15X | RM045/15X | RM030/15X | |||||
System Capacity | 60kVA | 40kVA | 20kVA | 90kVA | 45kVA | 30kVA | |||||
Power Module Capacity | 10kVA/10kW | 15kVA/15kW | |||||||||
Input | Dual Input | Standard | |||||||||
Phase | 3 Phase + Neutral + Ground, 380V/400V/415V(line-line) | ||||||||||
Input Voltage Range | 304~478Vac (line-line), full load;
228V~304Vac (line-line), load decreases linearly according to the min phase voltage |
||||||||||
Rate Frequency | 50/60Hz | ||||||||||
Input Frequency Range | 40Hz~70Hz | ||||||||||
Input PF | >0.99 | ||||||||||
Input THDi | <4% (100% Linear load) | ||||||||||
Bypass | Rate Voltage | 380/400/415Vac (line-line) | |||||||||
Rate Frequency | 50/60Hz | ||||||||||
Input Voltage Range | Settable, -40%~+25% | ||||||||||
Bypass Frequency Range | Settable, ±1Hz, ±3Hz, ±5Hz | ||||||||||
Bypass Overload | 125% long term operation; 130% for 10mins ;
150% for 1 min; >150% for 300ms |
110% long term operation; 125% for 5 mins; 150% for 1 min; >150% for 1s | |||||||||
Output | Rate Voltage | 380/400/415Vac (line-line) | |||||||||
Voltage Regulation | 1% for balance load; 1.5% for unbalance load | ||||||||||
Rate Frequency | 50/60Hz | ||||||||||
Frequency Precision | 0.1% | ||||||||||
Output PF | 1 | ||||||||||
Output THDu | <1%, Linear load; <5.5%, Non-linear load | ||||||||||
Crest Factor | 3:1 | ||||||||||
Inverter Overload | 110% for 1 hour; 125% for 10 mins; 150% for 1 min; >150% for 200ms | ||||||||||
Battery | Voltage | ±240Vdc | |||||||||
Battery Number | 40pcs (Settable: even number from 32 to 44) | ||||||||||
Voltage Precision | ±1% | ||||||||||
Charge Power | up to 20% * Output active power | ||||||||||
Battery Cold Start | Standard | ||||||||||
System | Efficiency | AC Mode | 95.0% | ||||||||
ECO Mode | 98.0% | ||||||||||
Battery Mode | 94.5% | ||||||||||
Display | 7.0″ color touch screen LCD + LED + keyboard | ||||||||||
IP Class | IP 20 | ||||||||||
Interface | RS232, RS485, Programmable Dry Contact | ||||||||||
Option | SNMP Card, Parallel kit, SPD, Power module with battery cold start function | ||||||||||
Temperature | Operation: 0~40 ℃ Storge: -40~70 ℃ | ||||||||||
Relative Humidity | 0~95% Non-condensing | ||||||||||
Altitude | <1000m. Within 1000m to 2000m, 1% power derating for every 100m rise. | ||||||||||
Noise (1 meter) | 56dB @ 50% load | ||||||||||
Applicable Standards | Safety: IEC/EN 62040-1 EMC: IEC/EN 62040-2 Performance: IEC/EN 62040-3 | ||||||||||
Physical | Weight (kg) | Cabinet | 70 | 51 | 42 | 70 | 55 | 42 | |||
Power module | 15.3 | 15.5 | |||||||||
Dimension W*D*H (mm) | Cabinet | 485*751*1033 | 485*697*575 | 485*697*398 | 485*751*1033 | 485*751*575 | 485*697*398 | ||||
Power module | 436*590*85 |